Four Propositions
- Alert volume in OT security monitoring is a property of architecture, not of tuning, and the architecture that produces manageable volume is available in OT for reasons that do not apply in corporate IT
- A small number of detection scenarios, expressed as violations of an enumerable set of legitimate behaviours, covers the great majority of realistic attack paths. Coverage measured in ATT&CK technique counts is the wrong metric and rewards the wrong design.
- Most operators know their monitoring does not see inside their OT networks, and record it as an engineering limitation. It is usually a commercial one. A large site has six to ten places worth watching, per-sensor licensing funds one or two, and the ones it funds are the cheapest to reach rather than the ones closest to the process. The gap is then priced per sensor, which is why it never closes.
- Threat hunting is a compensating control for environments where normal cannot be written down. In a deterministic process it should collapse into continuous conformance verification, with human judgement redirected from searching to validating the model. The framework can be satisfied this way, and the evidence is better, but only if the operator documents what replaced the hunt.
The paper closes with acceptance criteria that can be written into a specification, and questions an operator can answer internally, whether assessing an existing deployment or selecting a new one.
1 The lesson that the process industries have already paid for
1.1 Four incidents
Three Mile Island, Pennsylvania, March 1979
More than a hundred annunciators activated within minutes of the initiating fault, with no prioritisation separating the significant from the incidental and a logging printer running behind real time. Operators could not identify the condition that mattered. The incident opened the modern human factors literature on control room information design.
Texaco Milford Haven, Pembrokeshire, July 1994
A lightning strike caused a process upset, and for several hours afterwards operators were loaded with alarms at a rate exceeding one every two to three seconds. In the final eleven minutes before the explosion, two operators had to recognise, acknowledge and act on 275 alarms. Of the 2,040 alarms configured, most were set to high priority despite many being informational, so safety-critical alarms were not distinguishable from the rest.
Twenty-six people were injured and damage came to approximately £48 million. Operators had come to treat the distributed control system as more of a nuisance than a help. The HSE investigation and its associated research led directly to the writing of EEMUA 191.
Esso Longford, Victoria, September 1998
A heat exchanger failed by brittle fracture during a restart, killing two workers and injuring eight. Gas supply to the state of Victoria was severed for between nine and nineteen days. Among the Royal Commission's findings was that excessive alarm and warning systems had caused workers to become desensitised to possible hazardous occurrences. Desensitisation appears in the official record as a contributing factor rather than as later commentary.
Deepwater Horizon, Gulf of Mexico, April 2010
Eleven people died. The rig's general alarm had been set to inhibited for around a year:
detectors remained active and reported to the platform computer, but no audible or visual alarm was raised. The stated reason was that nobody wanted people woken at three in the morning by false alarms.
The operator's public position afterwards is the instructive part. Transocean's statement noted that too many false alarms can themselves be a safety risk. Both parties agreed that noise was dangerous. They disagreed only about the remedy, and the remedy applied was to silence the channel rather than to improve the quality of its signal.
1.2 How this became a legal test in the United Kingdom
EEMUA 191, first published in 1999 and now in its fourth edition, is not itself legislation. Its significance lies in how it is used.
No organisation is prosecuted for breaching EEMUA 191. Prosecution proceeds under the 1974 Act or the COMAH Regulations, and EEMUA 191 is the yardstick the inspector brings to establish whether the statutory duty was met.
1.3 The three principles that matter here
Two principles underpin the regulatory assessment: that major hazard safety must not depend on human response to an alarm, and that there is a limit to the amount of risk reduction an alarm can deliver. A third, equally load-bearing, is that every alarm must have a defined operator response, and that where no response can be defined the signal should not have been raised as an alarm at all.
Most organisations that hold themselves comfortably to EEMUA 191 in the control room would fail the same inspection outright on their security monitoring. The two systems sit in the same building, watch the same plant, draw on the same finite operator attention, and are held to entirely different standards
2 The same failure mode in security monitoring
In each of the cases below the signal existed, and the organisation did not act on it for reasons that were entirely rational at the time. None of these organisations lacked investment, and several were compliant with the standards applicable to them.
Maroochy Water Services, Queensland, 2000
A former contractor with insider knowledge of the SCADA installation issued radio commands to sewage pumping stations over several months. The symptoms were visible from the outset: loss of communication, loss of pump control, false alarms, suppressed alarms and altered pumping station configurations. It was initially thought that these were teething problems with the newly installed system.
The installer returned to reinstall and verify the system, operators physically inspected pipes and valves and found nothing, and visibility was limited because the system had no logging capability beyond simple status messages. Engineers attributed the faults to installation errors, and the reinstallation prolonged discovery. Approximately three months elapsed before an attack was suspected. Around 800,000 litres of raw sewage were released into parks, rivers and hotel grounds.
Mechanism: anomalies from a newly commissioned system were attributed to commissioning, and that attribution became the standing explanation for adversary activity.
Petro Rabigh, Saudi Arabia, 2017 (Triton / Trisis)
In June 2017 the plant's safety instrumented system tripped and shut the plant down. At the time this was believed to be a mechanical issue with the safety system. In August the plant shut down a second time, and the resulting investigation found the malware. The June investigation was subsequently assessed as insufficient, with the vendor having attributed the event to a mechanical failure of the emergency shutdown system rather than to a cyber attack.
At least six Triconex controllers had been compromised by malware built to co-opt the safety equipment during an emergency. The attackers appear not to have intended to trigger the shutdown that exposed them, having meant to retain persistent access until a moment of their choosing. Other indicators had been present, including remote desktop sessions to engineering workstations originating from the IT network.
Mechanism: a safety trip is a routine event with a routine explanation. The routine explanation was applied, and two months of adversary access followed.
North America, August 2003
FirstEnergy's alarm and logging system failed at 14:14 and was not restored until after the blackout. Unprocessed events queued behind the failed alarm process, the server hosting it folded within half an hour, and a backup server took over and also failed. Because the failure was silent, operators did not know they were working from stale information, and trusting their systems they discounted telephone calls warning them about deteriorating conditions on their own grid.
The joint task force concluded that without a functioning alarm system, control area operators failed to detect the tripping of facilities essential to the security of their control area. Fifty-five million people were affected.
Mechanism: the monitoring layer failed without announcing it, and its silence was read as an all-clear.
Merrimack Valley, Massachusetts, September 2018
The Ohio monitoring centre received a high-pressure alarm for the South Lawrence system at 16:04 and a second at 16:05. The controller reported it to the meters and regulations group in Lawrence at 16:06. The first emergency call came at 16:11, and the affected regulator was not shut down until 16:30, by which time gas had already flooded the low-pressure system.
The control room in Ohio had no means of stopping the flow without physically attending each individual valve, so gas continued to feed the over-pressurised area for a significant period after the alarms registered. One person was killed, twenty-two were injured and 131 structures were damaged.
Mechanism: detection was immediate and correct, and changed nothing, because those watching had neither the means nor the authority to intervene.
Target Corporation, United States, 2013
Included because it is the clearest documented case of a well-funded detection deployment producing correct output that nobody used. A $1.6 million deployment raised alerts at the highest severity on its scale for as many as five versions of the malware and identified the staging servers involved. The security operations centre did not react, and the automatic deletion function had been turned off by the security team.
The Senate kill chain analysis notes that the alert carried a generic name and that staff could have viewed it as a false positive. The company's own account was that the team evaluated the activity and determined that it did not warrant immediate follow-up.
Mechanism: an alert indistinguishable from the routine output of the same tool was treated as routine output. That is not a tuning or staffing failure. It is what occurs when an architecture cannot signal significance.
2.1 The pattern
3 What the regulator now asks
3.1 The statutory duty
The duty sits in the NIS Regulations 2018, and its wording rewards precise reading. Regulation 10(1) requires an operator of essential services to take appropriate and proportionate technical and organisational measures to manage risks posed to the security of the network and information systems on which their essential service relies. Regulation 10(2) requires appropriate and proportionate measures to prevent and minimise the impact of incidents, with a view to ensuring continuity of those services. Regulation 10(3) requires that those measures, having regard to the state of the art, ensure a level of security appropriate to the risk posed, and 10(4) requires operators to have regard to relevant guidance issued by their competent authority.
Three words carry the weight. Appropriate is relative to the risk actually faced, not to a catalogue of what is theoretically possible. Proportionate cuts both ways: it protects an operator from being required to do the unreasonable, and it equally undermines expenditure that cannot be tied to a risk it addresses. State of the art is a moving reference, which means an approach defensible in 2019 is not automatically defensible now.
Regulation 10 does not mention products, and nothing in it can be discharged by procurement.
3.2 Objective C in CAF v4.0
CAF v4.0 was published by the NCSC in August 2025 in consultation with the cyber regulators and oversight bodies that use the framework, and it is now used by nearly all UK cyber regulators as well as in the public sector through GovAssure. Published on 6 August 2025, it is the most significant revision since 2018 and adds 108 new Indicators of Good Practice. The structure is four objectives, fourteen principles and forty-one contributing outcomes, each rated Achieved, Partially Achieved or Not Achieved against its indicators. The framework is expected to gain statutory footing under the forthcoming Cyber Security and Resilience Bill.
Objective C, Detecting cyber security events, is where most of the change occurred. Principle C1, Security Monitoring, has been rearranged and expanded with an additional contributing outcome, while Principle C2 has been reduced to a single, clearer contributing outcome and is now titled Threat Hunting. Within C1 many indicators moved; the Generating Alerts outcome absorbed content from the former Monitoring Coverage and Identifying Security Incidents outcomes. The former Proactive Attack Discovery outcome was removed and replaced by Threat Hunting, which explicitly requires organisations to demonstrate understanding of user and system behaviour alongside the use of threat intelligence within security monitoring
OBJECTIVE C: WHAT IS ASSESSED, AND WHAT DECIDES WHETHER IT CAN BE EVIDENCED
3.3 The fatigue test
THE WORDING THAT CHANGES THE CONVERSATION
“Alert or triage fatigue is not present.”
Alarm fatigue is no longer an operational grumble or a vendor talking point. It is a condition that must be absent for a contributing outcome to be rated Achieved, in a framework used by almost every UK cyber regulator and heading for statutory footing.
This completes a loop that took the process safety community two decades to close. Milford Haven established that an unmanageable alarm rate is a contributory cause rather than a nuisance. EEMUA 191 turned the finding into a benchmark. HSE inspection turned the benchmark into a legal test. CAF v4.0 has now applied the equivalent test to security monitoring.
3.4 Two obligations pulling in opposite directions
The Generating Alerts outcome wants fewer false positives. The behaviour and threat hunting outcomes want deeper behavioural understanding and active search. A tool-led response to those demands is to collect more and alert more, which improves one outcome while damaging two others. That tension cannot be resolved by tuning. It is resolvable only by an architecture in which the number of things worth alerting on is small because the definition of normal is precise.
3.5 Complexity as an evidence liability
An outcome-based assessment does not ask whether a capability was purchased and installed. It asks whether alerts are triaged, whether they are understood, and whether they lead to decisions, and it expects evidence rather than description.
That creates an asymmetry easily missed at procurement stage. Every additional alert, suppression rule, tuning exception, vendor content update and integration handoff is a further thing about which an assessor may request evidence, and a further point at which the chain from signal to decision can be shown to break.
Complexity is not neutral under an outcome-based framework. It is a liability that must be funded with evidence indefinitely.
4 Alert volume as an architectural property
4.1 Determinism and enumerability
Hunting and detection in corporate IT are difficult because normal is unbounded. A corporate estate has tens of thousands of processes, arbitrary user behaviour and a software inventory that changes hourly. The space of legitimate behaviours cannot be written down, so detection relies on statistical anomaly inference and highly skilled analysts, and false positives are an unavoidable cost of doing business.
An OT process is deterministic. The devices are fixed, the communication relationships are fixed, the protocols are fixed, the operating envelope is defined, and change occurs at outage cadence under change control. Normal is genuinely enumerable.
The number of detection scenarios required is bounded by the number of ways the enumerated set can be violated, not by the number of techniques an adversary might employ.
4.2 Why technique counts are the wrong metric
Coverage claims are commonly expressed as the number of MITRE ATT&CK for ICS techniques a platform addresses. ATT&CK enumerates adversary methods, and its technique count reflects the variety of ways an objective can be achieved, which is a function of tooling diversity.
Detection does not observe methods. It observes effects on the environment. Where the set of legitimate behaviours is finite and enumerable, a large number of distinct techniques collapse onto a small number of observable effects. Counting techniques therefore measures the breadth of a vendor's content library rather than the operator's ability to detect anything, and it rewards designs that generate volume.
4.3 A scenario set
Eight behaviours, each expressed as a violation of something enumerable.
4.4 Where the set is weak
Any argument of this kind is credible only if its limits are named.
An organisation able to articulate those four residuals and state what it does about each is in a stronger position under an outcome-based assessment than one claiming broad technique coverage it has never tested.
5 Coverage geometry
5.1 A large site is not one vantage point
A large treatment works, compressor station, substation or terminal comprises several distinct network domains, and traffic in one is not visible from another. Ring topologies compound this: traffic between controllers on a resilient ring does not traverse an aggregation point at all, so no amount of uplink monitoring will observe it.
5.2 What an uplink-only deployment delivers
An uplink-only deployment covers one scenario properly and part of two others. The five scenarios that observe interaction with the process, corresponding to the Impair Process Control and Inhibit Response Function tactics, are not observable from it at all.
This is the mechanism behind the coverage gap that most operators record against the monitoring coverage outcome. It is not an oversight in the engineering.
6 Coverage economics
6.1 The licensing unit determines the architecture
A monitoring architecture is shaped by what it costs to extend. That constraint is rarely stated in a specification, and it determines the eventual shape of the deployment more than any technical property of the platform.
Where licensing is per sensor or per asset, each additional vantage point carries a marginal cost in licence and frequently in hardware. The rational procurement decision is therefore to purchase the smallest number of vantage points that produces a defensible-looking deployment, which in practice means one or two per site at the IT/OT uplink, because that is where a single sensor observes the greatest traffic volume.
The operator then discovers at first assessment that Objective C is asking about behaviour inside the OT network, and that closing the gap means multiplying the licence count by the number of internal segments. The gap register does not close, because closing it was never priced.
6.2 The arithmetic worth completing before comparing quotes
Line H is the figure that should be compared between suppliers, rather than the quoted price.
6.3 Two compounding consequences
Every physical sensor is an asset requiring protection. Eight appliances per site across twenty sites is 160 additional devices, frequently running operating systems the operator is contractually discouraged from patching, each holding credentials into the environment it monitors. Per-sensor licensing therefore presents a choice between an incomplete detection estate and a substantial unmanaged vulnerability estate. Software sensors hosted on existing capable hardware reduce that count materially, and where licensing does not penalise sensor count there is no reason to consolidate vantage points onto fewer devices than the topology requires.
Aggregation has physical limits as well as commercial ones. Industrial switches support a limited number of monitor sessions, TAP insertion on a live control network is a change with safety implications, and a ring topology offers no natural aggregation point. Even an operator willing to fund unlimited sensors will find that consolidating many vantage points onto few devices is not always achievable. The commercial model needs to permit the sensor count the topology dictates, rather than the topology being cut to fit the licence.
6.4 Alignment of interest
Under per-sensor licensing, the supplier's revenue increases each time the operator closes a coverage gap. This is not an allegation of bad faith; suppliers are entitled to charge for what they provide. It is an observation that the commercial structure places supplier interest and operator regulatory interest on opposite sides of the same decision, and that this becomes visible at renewal rather than at procurement.
Under per-application licensing with unlimited sensors, closing a coverage gap costs the operator an engineering change and costs the supplier nothing. The two interests point in the same direction.
SUPPLIER POSITION · DELTAFLARE
phoenix is licensed per application, with unlimited sensors, hardware or software, across as many vantage points as a site requires. The decision about where to sense is an engineering decision about where consequence lives, not a budget decision.
This is stated here because it is the mechanism by which the coverage argument above becomes actionable rather than aspirational. An operator should test the claim by asking what instrumenting one hundred additional segments would cost, in writing, of every supplier on their list.
6.5 Answering the obvious objection
More sensors means more data, and more data would appear to mean more alerts. If so, unlimited sensors and manageable alert rates cannot both be true.
They can, because they are independent. Alert volume is a function of how precisely normal is enumerated, not of how much is observed. In a deterministic process, additional vantage points make the enumeration tighter rather than looser: a controller ring that has never been observed contributes nothing to the definition of normal, whereas a controller ring that has been observed for a full operating cycle contributes a precise one. More sensing of a process that does not change yields more confident silence.
The claim is testable, and an operator should require measured alert rates from a multi-vantage-point deployment rather than accepting the reasoning on its own.
7 Threat hunting, and what replaces it
Threat hunting is a compensating control. Understanding what it compensates for explains why it is indispensable in corporate IT, and why in a deterministic process environment it is largely a symptom rather than a capability.
7.1 What hunting was invented to solve
Hunting emerged in enterprise IT for a specific reason: normal cannot be written down there. A corporate estate has tens of thousands of processes, arbitrary user behaviour and a software inventory that changes hourly. No specification of legitimate activity can be complete, so no automated check can be complete either, and the gap has to be covered by a person forming hypotheses about what an adversary would be doing and going to look.
That is a real skill answering a real need. It is also a consequence of the environment rather than a universal good practice. The discipline exists because the alternative is unavailable.
7.2 Why the need does not transfer to a static process
In a deterministic OT environment the alternative is available. The devices are fixed, the communication relationships are fixed, the protocols are fixed, the envelope is defined, and change happens at outage cadence under change control. Normal can be written down.
Once it can be written down, anything a hunter would go looking for can be expressed as a standing conformance check. Take a typical hunt hypothesis: did any node communicate with a peer outside the commissioned set during the last quarter. That is not a hunt. It is a continuously answerable question, and answering it by hand once a quarter is a worse version of answering it continuously.
A human periodically re-running the same reconciliation is not a detection capability. It is a manual substitute for a platform that should be performing that reconciliation without being asked.
7.3 What the human contribution is actually for
Redirecting the effort does not remove the person. It moves them from searching to two activities that automation cannot perform, both of which require an engineer rather than an analyst.
Defining the enumerated set. Someone has to decide what the legitimate communication relationships, permitted engineering sources, operating envelopes and change windows actually are. That is a specification exercise, and its quality determines everything downstream, including alert volume.
Validating that the set is still the truth. A model of normal decays whenever the plant changes. Revalidation is triggered by events rather than by the calendar, and its output is a corrected model rather than a report.
The last row is where most of the value sits. Every delta adjudicated as a model error makes the model tighter and the alert volume lower, which is the compounding mechanism that keeps a deployment inside triage capacity over years rather than drifting out of it.
7.4 The narrow case where human-led search still earns its place
Two of the residual risks named in section 4.4 cannot be enumerated away, because in both the adversary's behaviour is legitimate by the model's own definition.
- An insider operating inside the envelope. Commands from a permitted source, to a permitted device, within range, inside a change window. No conformance check can raise this, because nothing is non-conforming.
- Long-dwell passive reconnaissance. An adversary who observes and takes no action produces no violation to detect.
These warrant deliberate, hypothesis-led examination, with a process engineer present, a few times a year. That is a small and specific programme aimed at two named residuals, not a standing search function. Framing it that way is also more defensible than a general hunting programme, because it states what it is for.
7.5 Satisfying the framework without pretending
The framework asks for risk-led and intelligence-led search for hostile tactics, techniques and procedures, and for findings to be converted into detections. Continuous conformance answers the second half by construction: there is no interval between finding and detection, because the detection is the finding. It also produces more evidence than a hunt programme, and evidence covering the whole period rather than a handful of sampled days.
The risk is presentational rather than substantive. An operator who simply stops hunting and says nothing will be marked down, because the assessor will look for the activity in its recognisable shape and not find it. The claim has to be made deliberately and documented.
WHAT TO PUT IN FRONT OF AN ASSESSOR
- The enumerated model itself, with its provenance: who specified it, from what, and when.
- The validation record, showing the model was re-tested after each triggering event, with outcomes including the occasions on which nothing needed changing.
- The delta register, with dispositions, distinguishing engineering activity from model error from suspected intrusion.
- The residual risk statement, naming what conformance cannot cover and describing the small hypothesis-led programme that addresses it.
- The intelligence input record, showing how the threat picture informed which behaviours are enumerated and what the residual programme went looking for.
That pack is a stronger answer than twelve hunt reports, and it is consistent with a framework that asks for outcomes rather than for an activity performed in a particular shape. It should be assembled and labelled as the operator's answer to the hunting outcome, rather than left for an assessor to infer.
7.6 A caution worth stating
None of the above is an argument for doing less. An operator who drops hunting on a supplier's advice, and cannot then articulate what replaced it, is in a materially worse position than one running a token programme. The position is defensible only where the conformance model exists, is maintained, is evidenced, and where the two residuals are named and addressed. Absent those, the honest description is not that hunting was unnecessary but that it was dropped.
8 Acceptance criteria for a specification
Applicable regardless of supplier, and testable at procurement rather than discovered at renewal.
9 Questions for internal assessment
ALARM PERFORMANCE
- What is our current alert rate per analyst per hour, averaged and at peak, and how does it compare with the manageability threshold our own control room is held to?
- What proportion of alerts raised in the last quarter received a recorded human decision, as distinct from a closure code?
- What is our alert backlog, and what is the oldest unreviewed alert?
- Can every alert type our platform raises be tied to a defined response? For those that cannot, why are they configured as alerts?
- How many alerts fired during our last maintenance window, and what did we conclude from them?
SUPPRESSION
- How many alert types, sources, hosts or subnets are currently suppressed, shelved, allowlisted or auto-closed?
- For each, who authorised it, on what date, and when is it next due for review?
- If an adversary were operating within a suppressed category today, by what mechanism would we find out?
- Has any suppression decision been made because volume was unmanageable rather than because the alerts were wrong?
COVERAGE
- How many distinct vantage points does full coverage of our largest site require, and how many sensors do we have there?
- Which internal segments are instrumented, and which are not: engineering workstations, SCADA, controller ring, safety network, vendor access, inter-area links?
- Of the detection scenarios in our specification, how many are observable from our current sensor placement?
- Of our uninstrumented segments, for how many is the reason commercial rather than technical?
- What would it cost to instrument every vantage point at our three most consequential sites, in licence and in hardware?
- How many additional appliances would full coverage add to our estate, and who patches them?
EFFECTIVENESS
- Can we demonstrate, with evidence rather than supplier assertion, that a technique relevant to our environment would be detected today?
- When did we last test detection efficacy, as opposed to testing that sensors are online?
- What is our measured false positive rate, and if we do not have one, what have we used instead to judge whether the platform works?
- How would we know if our platform's analysis pipeline stopped processing? Does our health check prove analysis is occurring, or only that the appliance has power and a route?
- Where our platform detected something significant, would we have detected it at the alert rate recorded in question 1?
RESPONSE
- When an alert fires at 03:00, who has both the operational competence to interpret it and the authority to act before the next outage window?
- What actions can we take in response, given that isolating a running controller is not among them, and have those actions been written down?
- If our detection were perfect and our response capability were what it is today, what would have improved?
- Is our alerting routed to a team that operates the plant, or to one that operates the IT estate?
SUPPLIER RELATIONSHIP
- What is the network path by which detection content reaches our sensors, and how is that conduit documented in our zone and conduit model?
- Who is the named release authority for detection content taking effect inside our OT zones, and are they employed by us?
- Does our change control treat a detection content update as a change to the OT estate, and if not, why is it exempt?
- If we severed that conduit for ninety days, what would our supplier tell us our detection coverage had become?
- What is the patch status of the monitoring platform itself, and when did we last verify it independently?
- Can we attest to the authenticity and integrity of the detection logic currently running in our environment?
COMMERCIAL
- Our subscription cost tracks a unit. What does our detection efficacy track? Can we plot both over three years?
- Our process is deterministic and changes at outage cadence. What changed in the last billing period that improved our position?
- How many engineer-days per quarter do tuning and triage consume, and was that cost in the original business case?
- If the original business case was detection and what we principally use is the asset inventory, has the business case been re-tested against its new purpose?
- Does our licensing unit rise with our estate, our risk, or our use of the platform? Which of those should it track?
REGULATORY READINESS
- If our competent authority asked for evidence that a detected event led to a decision, what document would we produce?
- Under an outcome-based assessment, which is the stronger position: our current alert volume with our current triage capacity, or a smaller number of alerts each with a recorded decision?
- Which of our contributing outcomes under Objective C currently rest on the existence of a product rather than on evidenced practice?
- If a monitoring investment cannot be tied to a specific risk it reduces, on what basis is it appropriate and proportionate under Regulation 10?
10 Conclusion
The process safety community arrived at its conclusions the hard way, and the conclusions were not subtle: an alarm system nobody can keep pace with does not merely fail to help, it becomes part of the causal chain. That understanding is now embedded in how UK operators are inspected and how their statutory duties are judged.
Security monitoring in OT is a younger discipline applied to the same plant, in front of the same operators, drawing on the same finite attention. Little about the human factors differs. What has differed until recently is that security monitoring has not been required to demonstrate that its alarm systems are manageable.
Under CAF v4.0 that requirement has arrived, and it arrives alongside a second expectation that pulls in the opposite direction: deeper behavioural understanding and proactive discovery. Those two demands cannot be reconciled by tuning a system built to alert on everything theoretically possible. They can be reconciled by an architecture that enumerates what a deterministic process legitimately does, observes every place that process can be reached, and treats scarcity of alerts as evidence of precision rather than of blindness.
The questions in section 9 are the ones an assessor is moving towards asking. There is considerable advantage in having answered them first.